Winsen MEs-CO Carbon Monoxide Sensor

Winsen MEs-CO is a fuel-cell electrochemical carbon monoxide sensor that generates an output current proportional to CO concentration (Faraday’s law). It is designed for smart homes, commercial buildings, underground garages, and fire monitoring applications requiring reliable CO concentration measurement.

Highlights

  • Range: 0–1000 ppm (max 2000 ppm)
  • Sensitivity: 1.0–2.0 nA/ppm
  • Resolution: 1 ppm
  • Response time: T90 < 30 s

  • Lifespan: 7–10 years
Categories: ,

Description

MEs-CO is a fuel-cell type electrochemical sensor for carbon monoxide detection. Carbon monoxide and oxygen undergo corresponding redox reactions on the electrodes and generate a current. The output current is proportional to CO concentration and follows Faraday’s law.

Key Features

  • Low consumption
  • High precision
  • High sensitivity
  • Wide linear range
  • Good anti-interference ability
  • Long lifespan
  • Excellent repeatability and stability

Typical Applications

  • Smart homes
  • Commercial buildings
  • Underground garages
  • Fire monitoring and related safety systems

Technical Specifications

Item Specification
Detection gas CO (Carbon Monoxide)
Measurement range 0–1000 ppm
Max detecting concentration 2000 ppm
Sensitivity 1.0–2.0 nA/ppm
Resolution 1 ppm
Response time (T90) < 30 s
Load resistance (recommended) 500 / 1k / 2k Ω
Repeatability < 3% of output value
Output linearity Linear
Zero drift (-20 to 40 °C) ≤ 10 ppm
Temperature range -20 to 80 °C
Humidity range 15%–90% RH
Pressure range Standard atmosphere ± 10%
Lifespan 7–10 years

Cross-Sensitivity (Typical)

The MEs-CO sensor also responds to some gases other than CO. Typical response characteristics are listed below.

Interfering Gas Concentration Sensor Response (CO Equivalent)
H2S 100 ppm 0 ppm
C2H4 100 ppm 80 ppm
NO 35 ppm 6 ppm
NO2 5 ppm 0 ppm
C2H5OH 1000 ppm 0 ppm
Cl2 10 ppm 1 ppm
SO2 20 ppm 0.6 ppm
H2 500 ppm 40 ppm
NH3 50 ppm 1 ppm
CH3Cl 5 ppm 0 ppm
ETO 10 ppm 0 ppm
C6H6 100 ppm 1.5 ppm
C3H6O 100 ppm 3.5 ppm
CH3OH 200 ppm 0 ppm

Application Notes & Cautions

  • During installation, the lead can be welded, and the solder must not contact the sensor.
  • Before use, power on and age the sensor for more than 48 hours.
  • Do not disassemble the sensor.
  • Avoid contacting organic solvents (including silicone rubber and other adhesive), coatings, medicine, oil, and high concentration gases.
  • Do not encapsulate electrochemical sensors completely with resin materials and do not immerse in a non-oxygen environment; this can damage sensor function.
  • Do not use in corrosive gas environments; the sensor may be damaged.
  • Zero calibration should be performed in clean air.
  • Avoid gas inflow directly/vertically during testing and use.
  • Do not block or contaminate the inlet hole.
  • Avoid excessive impact or vibration.
  • Do not use the sensor if the shell is damaged or deformed.
  • In high concentration gas environments, recovery to the initial state can be slow after long-term exposure.
  • When storing the sensor, keep the working electrode and counter electrode in short circuit.
  • Do not encapsulate the sensor with hot melt adhesive or sealant whose curing temperature is higher than 80 °C.
  • Do not store or use the sensor in high concentration alkaline gas for a long time.

COMPARE SIMILAR PRODUCTS

Specification
Specification
Brand:
Winsen
Brand:
Winsen
Output:
PWM
Output:
UART
Principle:
Electrochemical
Principle:
Electrochemical
Range:
0~1000ppm
Range:
0~1000ppm
Response time:
<15S
Response time:
<15S
Target:
CO
Target:
CO